Sprinkler floor control assembly in an apartment building stairwell, with the stair sign on the wall beside it

Dallas Apartments: 81 Gauges and an Order to Comply

Another company's sprinkler inspection at a Dallas apartment building turned up 81 gauges, three hose caps, three extinguishers and a painted sprinkler, and Dallas Fire-Rescue followed with an order to comply. Paragon made the repairs and filed the repair report through The Compliance Engine.

Dallas, TX 2026

The city’s repair list

Another company inspected the sprinkler system at one building of a Dallas apartment community in January. A month later, Dallas Fire-Rescue sent the property an order to comply that listed:

  • 81 pressure gauges to replace
  • three brass 2.5-inch hose caps
  • three 2.5-pound ABC extinguishers
  • one painted sprinkler

The property hired us to make the repairs.

Repairs

Many of the gauges were on the floor control assemblies in the stairwells, on all three floors. Four were on the sprinkler riser. NFPA 25 calls for gauges to be replaced, or tested against a calibrated gauge, every five years.

We replaced all 81. We also put new brass caps on the stairwell hose valves, swapped the three extinguishers and replaced the painted sprinkler.

The report

Dallas Fire-Rescue takes corrections through The Compliance Engine. We submitted the repair report there with photos of the work, and left our service tag on the riser with “Corrected at YELLOW TAG” checked.

Additional context

  • Floor control assembly with a replaced pressure gauge
    Floor control assembly with a replaced pressure gauge
  • Four replaced pressure gauges in the sprinkler riser
    Four replaced pressure gauges in the sprinkler riser
  • Standpipe hose valve in a stairwell with a new brass cap
    Standpipe hose valve in a stairwell with a new brass cap
  • Paragon service tag reading 'repaired all yellow tagged deficiencies' with the corrected-at-yellow-tag box checked
    Paragon service tag reading 'repaired all yellow tagged deficiencies' with the corrected-at-yellow-tag box checked